Cracking the Code: Ensuring Fire Extinguisher Safety Beyond the Tag - What Every Safety Professional

In buildings of varying occupancy, classifications such as Business, Assembly, Minor Mercantile, Educational, Healthcare, Industrial, and other designations are all required to have portable fire extinguishers installed. As a safety professional, one verifies that the fire extinguisher installed is tagged, mounted, inspected monthly, and identified in a clear and obvious manner. The safety professional looks at the third-party contractor’s annual inspection tag and makes sure it is current.


But how do you know that the annual inspection of a fire extinguisher has been properly completed other than just looking at the date on a tag? The most consistent violations during inspections relate to fire extinguisher annual service and inspection. To make sure there is a clear understanding, let’s look at what the code says about fire extinguishers, specifically in the National Fire Protection Association’s NFPA 10.


“Periodic inspection or electronic monitoring of fire extinguishers shall include a check of at least the following items: (1) Location in designated place (2) Visibility of the extinguisher or means of indicating the extinguisher location (3) Access to the extinguisher (4) Pressure gauge reading or indicator in the operable range or position (5) Fullness determined by weighing or hefting (6) Condition of tires, wheels, carriage, hose and nozzle for wheeled extinguishers (7) Indicator for non-rechargeable extinguishers using push-to-test pressure indicator,” NFPA 10 Section 7.2.2 Inspection Procedures states.


NFPA 10 Section 7.3.2 requires the annual external examination of all extinguishers. This includes examining the physical condition of the portable fire extinguisher. An annual external visual examination of all fire extinguishers shall be made to detect obvious physical damage, corrosion and nozzle blockage; verify that the operating instructions are present, legible and facing forward; that the Hazardous Materials Identification System (HMIS) information is present and legible; and to determine if a 6-year interval examination or hydrostatic test is due (NFPA 10 Section 7.3.2.1).


Meanwhile, NFPA 10 Section 7.3.2.1.1 states, “At the time of the annual external visual examination, a check of at least the inspection items of 7.2.2 and the external examination items of 7.3.2.1 shall be conducted.” NFPA 10 Section 7.3.2.2 relates to seals or tamper indicators. At the time of the maintenance of a rechargeable fire extinguisher, the tamper seal shall be removed by operating the pull pin or locking device. 7.3.2.2.1 dictates that “after the applicable maintenance procedures are completed, a new listed tamper seal shall be installed.”


When the portable fire extinguisher contractor conducts their annual inspection, do they pick up the fire extinguishers or just change the tag? In many cases, they just change the tag, which does not comply with NFPA 10 standards. One might ask, “How can you tell?”


Sometimes, the accumulation of dust can indicate that the portable fire extinguisher has not been picked up for some time. Manufacturers recommend shaking or using a rubber mallet to tamp the extinguisher monthly to prevent the powder from settling. To ensure proper functionality of the portable fire extinguisher, shaking or using a rubber mallet should be done annually by a third-party fire extinguisher contractor. If proper annual inspection and maintenance is not done, the effectiveness of the fire extinguisher will decrease from year to year.


Another issue that is commonly identified for portable fire extinguishers is that every 6 years, a dry chemical fire extinguisher must have the powder changed. The extinguisher must be dumped, internally inspected, and refilled with a dry chemical suppression agent. The calculation starts with the portable fire extinguisher’s date of manufacture. Rechargeable dry chemical extinguishers are stored-pressure fire extinguishers subject to a 12-year hydrostatic test.


NFPA 10 Section 7.3.6 requires the six-year internal examination of certain types of extinguishers. Every 6 years, stored-pressure fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the applicable internal and external examination procedures as detailed in the manufacturer’s service manual and this standard.


Suppose the safety auditor or inspector does not cite that a portable fire extinguisher is overdue for required service. In that case, they have missed a significant Fire Code violation that directly affects the overall safety of the facility it is installed in. Portable fire extinguishers are required in buildings because they are a stop-gap measure to prevent a small fire from becoming a big fire. Once the fire sprinkler system is activated, firefighters are at a disadvantage.


If a fire becomes large enough to activate the automatic fire sprinkler system, responding firefighters risk their lives and health to save others and protect property. If a fire is extinguished when it is small, the property is protected, and lives can be saved; the lives saved can include employees, staff, patrons, and, yes, firefighters.


Safety inspectors work to ensure the safety of employees, staff, and patrons of a given facility. Safety Professionals must be aware of fire protection systems and fire safety deficiencies.



Cracking the Code: Ensuring Fire Extinguisher Safety Beyond the Tag - What Every Safety Professional
Cracking the Code: Ensuring Fire Extinguisher Safety Beyond the Tag - What Every Safety Professional

Comments


bottom of page